Water disinfection with ozone, copper and silver ions, and temperature increase to control Legionella:: seven years of experience in a university teaching hospital

期刊

JOURNAL OF HOSPITAL INFECTION
卷 60, 期 1, 页码 69-72

出版社

W B SAUNDERS CO LTD
DOI: 10.1016/j.jhin.2004.10.016

关键词

Legionella; water; desinfection

向作者/读者索取更多资源

The efficacy of ozonation, copper-silver ionization and increased temperature in controlling Legionella spp. in the hot water distribution networks of a university hospital was evaluated. Two separate water distribution networks were studied; network 1 which supplies the surgical intensive care units, and network 2 which supplies the medical intensive care units and the emergency room. Network 1 has been disinfected by ozonation since 1995, and network 2 has been disinfected by ionisation since 1999. The hot water temperature was increased from 50 to 65 degrees C in 1998 and 2000 in networks 1 and 2, respectively. Water samples and swabs of the water outlets were cultured for Legionella spp. between four and six times each year, providing data before and after implementation of the disinfection procedures. There was no significant difference in the proportion of samples positive for Legionella spp. after ozonation in network 1 or after ionization in network 2. In both networks, there was a significant reduction in legionella isolates after increasing the hot water temperature to 65 degrees C. Maintaining the hot water temperature above 50 degrees C throughout both networks proved to be the most effective control measure in our hospital. (c) 2004 The Hospital Infection Society. Published by Elsevier Ltd. All rights reserved.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.5
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据