4.8 Article

The use of variable speed drives for cost-effective energy savings in South African mine cooling systems

期刊

APPLIED ENERGY
卷 111, 期 -, 页码 16-27

出版社

ELSEVIER SCI LTD
DOI: 10.1016/j.apenergy.2013.04.061

关键词

Variable speed drives; Mine cooling systems; Energy savings; Emission reductions

向作者/读者索取更多资源

An industrial energy efficiency improvement through the introduction of modern technology is an important demand-side management initiative. Cooling systems on South African mines have been identified as large electricity consumers. There is significant potential for energy efficiency improvement by the widespread introduction of variable speed drive (VSD) technology. An energy audit was conducted on 20 large mine cooling systems and potential savings and feasibility indicators were calculated. A pilot implementation study was also done on one mine to experimentally validate the estimated savings. In this paper, the results of the audit, the potential savings and the pilot study results are presented. It is shown that large-scale implementation of VSDs on mine cooling system pumps and fans is economically viable. A total annual electrical energy saving of 144,721 MW h, or 32.2%, can be achieved. An annual cost saving of US$6,938,148 and CO2 emissions reduction of 132 Mton is possible. The implementation of VSDs on mine chiller compressors will also result in large energy savings, but is not economically feasible at present. Results of the pilot study indicate an electricity savings of 29.9%. The results are important to decision makers and indicate the significant impact that widespread VSD usage on mine cooling systems can have on South African mine sustainability. (C) 2013 Elsevier Ltd. All rights reserved.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.8
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据