4.8 Article

Cooling dominated Hybrid Ground Source Heat Pump System application

期刊

APPLIED ENERGY
卷 94, 期 -, 页码 41-47

出版社

ELSEVIER SCI LTD
DOI: 10.1016/j.apenergy.2012.01.031

关键词

HGSHPS; Hybrid; Borehole; Cooling tower; Packing

向作者/读者索取更多资源

A cooling dominated Hybrid Ground Source Heat Pump System (HGSHPS) is utilized to cover the energy demands of an office building. The energy demands are computed by TRNSYS 16.1, considering two different scenarios, based on different glazing properties. A ground loop consisted of a rectangular field of 15 borehole heat exchangers is utilized to cover building loads. GLD 2009 sizing software calculates borehole length setting two different fixed temperatures for the heat carrier fluid entering heat pump, 30 degrees C and 33 degrees C. Assuming different cooling tower capacity, the desired flow rate is estimated for a cooling range of 5.7 degrees C (the difference between the water inlet and outlet temperature). A MATLAB code is created to calculate the required pressure drop per packing height of cooling tower for four packings in different operating conditions. (c) 2012 Elsevier Ltd. All rights reserved.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.8
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据