4.6 Article

Field study on occupant comfort and the office thermal environment in rooms with displacement ventilation

期刊

INDOOR AIR
卷 15, 期 3, 页码 205-214

出版社

WILEY-HINDAWI
DOI: 10.1111/j.1600-0668.2005.00337.x

关键词

field study; displacement ventilation; human response; draught; vertical temperature difference; perceived air quality

向作者/读者索取更多资源

A field survey of occupants' response to the indoor environment in 10 office buildings with displacement ventilation was performed. The response of 227 occupants was analyzed. About 24% of the occupants in the survey complained that they were daily bothered by draught, mainly at the lower leg. Vertical air temperature difference measured between head and feet levels was less than 3 degrees C at all workplaces visited. Combined local discomfort because of draught and vertical temperature difference does not seem to be a serious problem in rooms with displacement ventilation. Almost one half (49%) of the occupants reported that they were daily bothered by an uncomfortable room temperature. Forty-eight per cent of the occupants were not satisfied with the air quality.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.6
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据