3.8 Article

Experimental investigation of oil retention in air conditioning systems

出版社

ELSEVIER SCI LTD
DOI: 10.1016/j.ijrefrig.2005.03.012

关键词

air conditioning; refrigerating system; compression system; oil; measurement; oil return; compressor

向作者/读者索取更多资源

In air conditioning and refrigeration systems a small amount of oil is carried with the refrigerant and is retained in the system components. Oil retention characteristics in the condenser, evaporator, liquid and suction lines were measured and are presented and discussed here. Refrigerants R22, R410A, and R134a with miscible and non-miscible lubricants were considered to investigate oil retention physics in the widest possible range of transport properties. A parametric analysis in the suction line showed that oil retention depends on the oil mass fraction, vapor refrigerant mass flux, mixture viscosity ratio and orientation of the pipe. In the suction line, an increase in mixture viscosity of about 55% caused a rise in oil retention in the range of 50%, depending on the oil mass fraction. Oil retention in the upward vertical suction line is about 50% higher than in the horizontal line at similar conditions. (c) 2005 Elsevier Ltd and IIR. All rights reserved.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

3.8
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据