4.5 Review

Analysis based on EU Regulation No 517/2014 of new HFC/HFO mixtures as alternatives of high GWP refrigerants in refrigeration and HVAC systems

期刊

INTERNATIONAL JOURNAL OF REFRIGERATION
卷 52, 期 -, 页码 21-31

出版社

ELSEVIER SCI LTD
DOI: 10.1016/j.ijrefrig.2014.12.021

关键词

Refrigeration; Air conditioning; GWP; EU Regulation No 517/2014; HFO/HFC mixtures; HFC replacement

资金

  1. Ministerio de Educacion, Culture y Deporte through Becas y Contratos de Formacion de Profesorado Universitario del Programa Nacional de Formacion de Recursos Humanos de Investigacion [FPU12/02841]

向作者/读者索取更多资源

The EU Regulation No 517/2014 is going to phase-out most of the refrigerants commonly used in refrigeration and air conditioning systems (R134a, R404A and R410A) because of their extended use and their high GWP values. There are very different options to replace them; however, no refrigerant has yet imposed. In this paper we review and analyze the different mixtures proposed by the AHRI as alternative refrigerants to those employed currently. These mixtures are composed by HFC refrigerants: R32, R125, R152a and R134a; and HFO refrigerants: R1234yf and R1234ze(E). It is concluded, from the theoretical analysis, that most of the new HFO/HFC mixtures perform under the HFC analyzed (although some experimental studies show the contrary) and, in most cases, do not meet the GWP restrictions approved by the European normative. Furthermore, some of the mixtures proposed would have problems due to their flammability. (C) 2015 Elsevier Ltd and IIR. All rights reserved.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.5
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据