4.5 Article

A general model for two-stage vapor compression heat pump systems

出版社

ELSEVIER SCI LTD
DOI: 10.1016/j.ijrefrig.2014.12.005

关键词

Heat pump; Two-stage system; Model; Refrigerant; Injection

资金

  1. Research Fund for the Doctoral Program of Higher Education of China [20120041110006]

向作者/读者索取更多资源

Two-stage vapor compression technology has high potential of performance improvement for cold climate heat pumps, and there are several types of inter-stage configurations that need to be evaluated before making a choice. A general model of these configurations is first derived from a subcooler cycle and then is extended to be capable of evaluating many other inter-stage configurations by employing an input domain. The model is solved with a sequential algorithm and an analytical initial solution of the intermediate pressure is presented. After an experimentally validation with additional calculations of the sub-cooling parameter, the evaporating and condensing pressure, this general model is then used in the performance comparison and analysis of eight different inter-stage configurations. At last, case studies show that, this general model is capable of performing performance comparison among cycles with different types of inter-stage configurations, as well as refrigerant selection and operational analysis. (C) 2014 Elsevier Ltd and IIR. All rights reserved.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.5
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据