4.5 Article

Two-phase refrigerant distribution in an intermediate header of a parallel flow minichannel heat exchanger

出版社

ELSEVIER SCI LTD
DOI: 10.1016/j.ijrefrig.2015.06.023

关键词

Flow distribution; Heat exchanger; Header; Intermediate

资金

  1. Incheon National University Research Grant

向作者/读者索取更多资源

Refrigerant R-410A distribution in a two pass evaporator with intermediate header was investigated. The number of tubes was 10 for the first pass and 12 for the second pass. Tests were conducted for the mass flux from 73 to 143 kg m(-2) s(-1), quality from 0.4 to 0.6. In the intermediate header, two-phase mixture out of the first pass is merged and then redistributed to the second pass. More liquid is forced downstream as mass flux or quality increases yielding better flow distribution. Effect of insertion device in the inlet header was also investigated. Efforts were made to develop correlations to predict the liquid or gas distribution in a header with limited success. Header pressure drop data are also provided. (C) 2015 Elsevier Ltd and International Institute of Refrigeration. All rights reserved.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.5
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据