Prospective 3-year surveillance for nosocomial and environmental Legionella pneumophila:: Implications for infection control

期刊

INFECTION CONTROL AND HOSPITAL EPIDEMIOLOGY
卷 27, 期 5, 页码 459-465

出版社

CAMBRIDGE UNIV PRESS
DOI: 10.1086/503642

关键词

-

向作者/读者索取更多资源

Objectives. To perform a 3-year, prospective surveillance program for legionnaires disease (LD) in a large university hospital in Rome, and to assess the usefulness of the hospital water monitoring program in predicting the risk of nosocomial LD. Methods. Samples from patients with new cases of nosocomial pneumonia were sent for legionella laboratory investigations. Meanwhile, water samples for bacteriological analysis were collected every 6 months from high- and medium-risk hospital wards (10 in total). Legionella pneumophila isolates collected were serotyped and analyzed by pulsed-field gel electrophoresis. Results. From June 2001 through May 2004, the pneumonia surveillance identified one case of nosocomial LD among 43 cases of nosocomial pneumonia (2.3%). Environmental investigations detected L. pneumophila in 12 (18.7%) of the 64 water samples, of which 50% belonged to serogroup 1. The L. pneumophila count and the percentage of positive locations never exceeded 10(2) colony-forming units/L and 20%, respectively, except when the LD nosocomial case occurred (positive water samples, 40%;L. pneumophila count, < 10(2) colony-forming units/L). Genotyping showed 3 prevalent clones of L. pneumophila in the water distribution network, of which one persisted over the 3 years. One clone contained 3 different L. pneumophila serogroups (2, 4, and 6). Conclusions. The low incidence of nosocomial cases of LD appears to be associated with a low percentage (< 20%) of positive water samples per semester and with a low contamination level (< 102 colony-forming units/L). An infection control system for nosocomial LD should, therefore, be based on both environmental and clinical surveillance, together with the appropriate maintenance of the hospital water distribution system.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.4
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据