4.7 Article

Improving the efficiency of natural draft cooling towers

期刊

ENERGY CONVERSION AND MANAGEMENT
卷 47, 期 9-10, 页码 1086-1100

出版社

PERGAMON-ELSEVIER SCIENCE LTD
DOI: 10.1016/j.enconman.2005.07.012

关键词

cooling tower; entropy generation; exergy destruction; cooling tower efficiency; heat transfer

向作者/读者索取更多资源

This study shows how the efficiency of a natural draft cooling tower can be improved by optimising the heat transfer along the cooling tower (CT) packing using a suitable water distribution across the plane area of the cooling tower. On the basis of cooling air measurements, it is possible to distribute the water in such a way that it approaches the optimal local water/air mass flow ratio and ensures the homogeneity of the heat transfer and a reduction of entropy generation, thus minimising the amount of exergy lost. The velocity and temperature fields of the air flow were measured with the aid of a remote control mobile robot unit that was developed to enable measurements at an arbitrary point above the spray zone over the entire plane area of the cooling tower. The topological structures of the moist air velocity profiles and the temperature profiles above the spray zone were used as input data for calculation of the local entropy generation in the tower. On the basis of the measured boundary conditions, a numerical analysis of the influence of the water distribution across the cooling tower's plane area on entropy generation and exergy destruction in the cooling tower was conducted. (c) 2005 Elsevier Ltd. All rights reserved.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据