3.9 Article

Protection of occupants from exhaled infectious agents and floor material emissions in rooms with personalized and underfloor ventilation

期刊

HVAC&R RESEARCH
卷 13, 期 1, 页码 23-38

出版社

TAYLOR & FRANCIS INC
DOI: 10.1080/10789669.2007.10390942

关键词

-

向作者/读者索取更多资源

The performance of two personalized. ventilation systems supplying air at the breathing zone was tested in conjunction with underfloor ventilation generating two different airflow patterns in a full-scale test room. Two breathing thermal manikins were used to simulate occupants. The distribution of pollutants associated with exhaled air and floor material emissions was evaluated at various combinations of personalized and underfloor airflow rates. Compared to underfloor ventilation alone, personalized and underfloor ventilation provided excellent protection Of seated occupants from any pollution, while the concentration of exhaled air pollution increased in the room. The two types of personalized ventilation performed differently. Subsequent analyses of airborne infection transmission risk indicated that personalized ventilation could become a supplement to traditional methods of infection control.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

3.9
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据