期刊
ENVIRONMENTAL MONITORING AND ASSESSMENT
卷 125, 期 1-3, 页码 271-279出版社
SPRINGER
DOI: 10.1007/s10661-006-9519-8
关键词
Cooling tower; Legionella pneumophila; Legionnaires' disease; biofilm; biofouling
Cooling towers have the potential to develop infectious concentrations of Legionella pneumophila. Legionella counts increases where biofilm and warm water temperatures are present. In this study, biofilm associated L. pneumophila and heterotrophic bacteria were compared in terms of material dependence. Model cooling tower system was experimentally infected by L. pneumophila standard strain and monthly monitored. Different materials were tested for a period of 180 days. The lowest L. pneumophila and heterotrophic plate counts were measured on plastic polymers, whereas L. pneumophila and heterotrophic bacteria were accumulated rapidly on galvanized steel surfaces. It can be concluded that selection of plastic polymers, as a manufacturing material, are suitable for recirculating water systems.
作者
我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。
推荐