FIRE TECHNOLOGY
卷 43, 期 1, 页码 45-75出版社
SPRINGER
DOI: 10.1007/s10694-007-0007-7
关键词
atria; smoke management; make-up air; entrainment
This study examines the possible effects of various make-up air supply arrangements and velocities in an atrium smoke management system. Variations include velocities ranging from 0.5 to 3.0 m/s. The arrangement of make-up air supply injection points include symmetrically located vents placed low in the spaced, an array of vents distributed from the floor to the ceiling, and asymmetrically located vents. Fire Dynamic Simulator version 4.06 is applied to simulate ten scenarios in a 30.5 m cubical domain with a fire source simulating a stack of pallets with an approximate peak heat release rate of 5 MW. Results show that make-up air supply velocities should be diffused such that little to no velocity effects reach the fire. Make-up air should be supplied to the fire symmetrically for the best chance of not disturbing the fire plume. Disturbing the fire and smoke plume results in a significant increase in the smoke production rate, as evidenced by a deeper smoke layer.