4.6 Article

Risk factors for contamination of hotel water distribution systems by Legionella species

期刊

APPLIED AND ENVIRONMENTAL MICROBIOLOGY
卷 73, 期 5, 页码 1489-1492

出版社

AMER SOC MICROBIOLOGY
DOI: 10.1128/AEM.02191-06

关键词

-

向作者/读者索取更多资源

The Legionella colonization frequency at 385 Greek hotel hot and cold water distribution systems was 20.8%. Legionella contamination was associated with the presence of an oil heater (odds ratio [OR] = 2.04, 95% confidence interval [CI] = 1.12 to 3.70), with the sample temperature (OR = 0.26, 95% CI = 0.1 to 0.5), with seasonal operation (OR = 3.23, 95% CI = 1.52 to 6.87), and with the presence of an independent disinfection system (OR = 0.30, 95% CI = 0.15 to 0.62). The same water temperatures, free-chlorine levels, and pHs differently affect the survival of various Legionella spp.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.6
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据