期刊
IEEE TRANSACTIONS ON POWER DELIVERY
卷 22, 期 2, 页码 795-800出版社
IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC
DOI: 10.1109/TPWRD.2007.893376
关键词
distance measurement; pattern recognition; protective relay
This paper describe a new ultra-high speed protection algorithm for traveling-wave distance protection for transmission lines, based on pattern recognition of the first wavefront that arrives at the relay location due to fault. The algorithm uses principal component analysis (PCA) to preprocess data from the power system in order to eliminate redundant information and enhance hidden patterns in the traveling waves for internal and external faults. The algorithm was proven using PSCAD/EMTDC simulations in a three-phase 400-kV power system considering critical fault cases. The results show the feasibility to implement this algorithm for transmission-line ultra-high speed protection.
作者
我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。
推荐