A performance assessment of airborne infection isolation rooms

期刊

AMERICAN JOURNAL OF INFECTION CONTROL
卷 35, 期 5, 页码 324-331

出版社

MOSBY-ELSEVIER
DOI: 10.1016/j.ajic.2006.10.012

关键词

-

向作者/读者索取更多资源

Background: Airborne infection isolation rooms (AIIRs) help prevent the spread of infectious agents in hospitals. The performance of 678 AIIRs was evaluated and compared with construction design guidelines. Methods: The pressure differentials (Delta P) between the isolation rooms and adjacent areas were measured, and ventilation and construction details were recorded for each room. Ultrafine particle concentrations were evaluated in the rooms, surrounding areas, and ventilation systems serving the rooms. Measurements were analyzed as a function of room parameters. Results: Only 32 % of the isolation rooms achieved the recommended Delta P of -2.5 Pascals (Pa) relative to surrounding areas. AIIRs with solid ceilings had an average Delta/P of -4.4 Pa, which was significantly higher than the average Delta P of -2.0 Pa for rooms with dropped ceilings (P = .0002). Isolation room ultrafine particle concentrations were more highly correlated with particle levels in surrounding areas (R-2 = 0.817) than in the ventilation systems serving the rooms (R-2 = 0.441). Almost all ventilation filters serving AIIRs collected fewer particles than anticipated. Conclusion: The results indicate that hospitals are not all maintaining AIIRs to correspond with current guidelines. The findings also support the contention that having tightly sealed rooms helps maintain appropriate pressure differentials.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.5
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据