3.9 Article

Near-optimal control strategies for hybrid cooling plants

期刊

HVAC&R RESEARCH
卷 13, 期 4, 页码 599-622

出版社

AMER SOC HEATING REFRIGERATING AIR-CONDITIONING ENG, INC,
DOI: 10.1080/10789669.2007.10390974

关键词

-

向作者/读者索取更多资源

This paper develops and evaluates a set of operating strategies that when implemented together provide near-optimal performance for hybrid cooling plants in terms of operating costs. A hybrid chiller plant employs a combination of chillers that are powered by electricity and natural gas. Operating cost minimization for hybrid plants must account for effects of electrical and gas energy costs, electrical demand costs, and differences in maintenance costs associated with different chillers. Control strategy development was facilitated by separating hourly energy cost minimization from the problem of determining trade-offs between monthly energy and demand costs. A demand constraint is set for each month based upon a heuristic strategy and energy cost optimal strategies that attempt to satisfy the demand constraint are applied for cooling tower and chiller control at each decision interval. Simulated costs associated with the individual control strategies compare well with costs for optimal control.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

3.9
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据