4.6 Article

A power line signaling based technique for anti-islanding protection of distributed generators - Part I: Scheme and analysis

期刊

IEEE TRANSACTIONS ON POWER DELIVERY
卷 22, 期 3, 页码 1758-1766

出版社

IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC
DOI: 10.1109/TPWRD.2007.899618

关键词

distributed generation; distributed generation (DG) interconnection; islanding detection

向作者/读者索取更多资源

Anti-islanding protection of distributed generators (DG) is a significant technical barrier to the emerging DG industry. This paper presents an innovative power line signaling based anti-islanding scheme developed in response to the challenge. The scheme broadcasts a signal from a substation to the DG sites using the distribution feeders as the signal paths. A DG is considered as islanded from the upstream system if the signal cannot be detected at the DG site. The proposed scheme has been evaluated using analytical, simulation and field tests. The results are very promising. This paper presents the main ideas of the scheme and its design considerations. Methods to create and detect the signals are shown and their performances are analyzed.