4.7 Article

Patient thermal comfort requirement for hospital environments in Taiwan

期刊

BUILDING AND ENVIRONMENT
卷 42, 期 8, 页码 2980-2987

出版社

PERGAMON-ELSEVIER SCIENCE LTD
DOI: 10.1016/j.buildenv.2006.07.035

关键词

thermal comfort; hospital environment; field experiment

向作者/读者索取更多资源

This study examines the comfort criteria of ASH RAE Standard 55-2004 for their applicability in hospital environments. Through an extensive field survey conducted in a university hospital in Taiwan, 927 sets of data have been collected. Above half of the measured samples failed to meet the specifications of Standard 55 comfort zone due to improper humidity control. Acceptability votes by patients exceeded the Standard's 80% criterion, regardless of whether the physical conditions were in or out of the comfort zone. Thermal neutrality, preference and comfort range are compared with other studies conducted in office environments and Standard 55 criteria. Results of chi-square tests revealed that patients' physical strength significantly effected their thermal requirements. The net effect of health yields a marked difference in thermal neutrality and preference, and also in the comfortable temperature range. (c) 2006 Elsevier Ltd. All rights reserved.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据