4.7 Article

Shock circle model for ejector performance evaluation

期刊

ENERGY CONVERSION AND MANAGEMENT
卷 48, 期 9, 页码 2533-2541

出版社

PERGAMON-ELSEVIER SCIENCE LTD
DOI: 10.1016/j.enconman.2007.03.024

关键词

refrigeration system; ejector; modeling; velocity distribution; shock circle; performance evaluation

向作者/读者索取更多资源

In this paper. a novel shock circle model for the prediction of ejector performance at the critical mode operation is proposed. By introducing the shock circle at the entrance of the constant area chamber, a 2D exponential expression for velocity distribution is adopted to approximate the viscosity flow near the ejector inner wall. The advantage of the shock circle analysis is that the calculation of ejector performance is independent of the flows in the constant area chamber and diffuser. Consequently, the calculation is even simpler than many 1D modeling methods and can predict the performance of critical mode operation ejectors much more accurately. The effectiveness of the method is validated by two experimental results reported earlier. The proposed modeling method using two coefficients is shown to produce entrainment ratio, efficiency and coefficient of performance (COP) accurately and much closer to experimental results than those of 1D analysis methods. (c) 2007 Elsevier Ltd. All rights reserved.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据