4.7 Article

Spray cooling on micro structured surfaces

期刊

INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER
卷 50, 期 19-20, 页码 4089-4097

出版社

PERGAMON-ELSEVIER SCIENCE LTD
DOI: 10.1016/j.ijheatmasstransfer.2006.12.037

关键词

spray cooling; micro structures; contact line; TLCs; surface temperature distribution

向作者/读者索取更多资源

Spray cooling experiments have been performed on a smooth heater surface. The working fluid water was atomized through a full cone nozzle into a low pressure spray chamber. Different coolant mass fluxes were studied by varying the distance between nozzle and heater. Observations obtained with an infrared camera indicated that the length of the three phase contact line increased as the heat flux in the experiments was raised. Motivated by this finding, the effect of different micro structured surfaces, which lead to an increase in the three phase contact line, on the spray cooling performance was studied. The micro structures consisted of micro pyramids with different heights. A significant enhancement in the heat transfer performance due to the surface structures could be observed, especially at low coolant fluxes. Additionally. high spatial resolution temperature measurements oil a smooth heater using thermochromic liquid crystals were obtained. These measurements indicate high local temperature gradients for a regime where the coolant film on the heater is ruptured. (C) 2007 Elsevier Ltd. All rights reserved.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据