4.6 Article

Metal oxide surge arrester condition monitoring based on analysis of leakage current components

出版社

ELSEVIER SCI LTD
DOI: 10.1016/j.ijepes.2014.10.052

关键词

Metal oxide surge arrester; Condition monitoring; Indicator; Leakage current

向作者/读者索取更多资源

This paper presents proper indicators for evaluation of the surge arrester condition based on the leakage current analysis. Maximum amplitude of fundamental harmonic of the resistive leakage current (I-mr1), maximum amplitude of third harmonic of the resistive leakage current (I-mr3) and maximum amplitude of fundamental harmonic of the capacitive leakage current have been used as indicators for surge arrester condition monitoring. The effects of operating voltage fluctuation, third order of voltage harmonic, over-voltage and varistor aging have been investigated to show the ability of introduced indicators for accurate diagnostic of arrester's conditions. In order to have accurate values of stray capacitors, 3D-FEM has been used. Moreover, surge arrester model for calculating leakage current has been performed in ATP-EMTP. In addition, the signal processing has been done using MATLAB software. This study shows that the introduced indicators are proper criteria for surge arrester condition monitoring. (C) 2014 Elsevier Ltd. All rights reserved.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.6
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据