4.7 Article

Performance analysis of a wind tower in combination with an underground channel

期刊

SUSTAINABLE CITIES AND SOCIETY
卷 37, 期 -, 页码 427-437

出版社

ELSEVIER SCIENCE BV
DOI: 10.1016/j.scs.2017.12.002

关键词

Wind tower; Underground channel; Ventilation; Passive cooling; Renewable energy; HVAC

向作者/读者索取更多资源

In the present work, a new method was introduced in order to improve the performance of wind towers. In hot seasons, underground temperature is lower than that of the surface and it can be used as a free cooling source. Accordingly, in this work, the use of a wind tower in combination with an underground channel for passing the air was introduced and investigated. This research was done for two cases of dry and wet channels. In order to solve this problem numerically, governing equations were discretized using finite volume method, SIMPLE algorithm was used for pressure-velocity coupling and k-epsilon model was chosen as turbulent model. Considering the weather conditions of Yazd in Iran as a sample of the regions where using wind towers is common, this study concluded that using dry or/and wet channels, the entrance air temperature was reduced from 42 degrees C to 34.4 degrees C and 26.6 degrees C, respectively. Using the wet channel, the relative humidity of air increased by 52%, from the initial value of 14% to 66%, and the water consumption of 0.006 kg/s and air mass flow rate of 0.8466 kg/s were achieved. Results showed that this method is efficient due to thermal comfort conditions.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据