Impact of Conductor Surface Type and Rain Intensity on HVDC Corona Losses

期刊

IEEE TRANSACTIONS ON POWER DELIVERY
卷 30, 期 5, 页码 2284-2292

出版社

IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC
DOI: 10.1109/TPWRD.2015.2424315

关键词

Corona; HVDC; ion current; rain

资金

  1. Amprion GmbH, Germany

向作者/读者索取更多资源

This paper presents the results of a series of indoor laboratory experiments carried out on dc-energized overhead conductors subjected to simulated rainfall. In a first set of experiments, the impact of rain intensity on the corona onset voltage and total corona losses was investigated. With regard to the onset voltage, no significant impact was observed, whereas a weak positive correlation with total corona losses could be established. In a second set of experiments, the impact of different conductor types on the same two quantities was examined. The most notable result is that the combined use of Z-profiled-strands and sand-blasted surfaces lead to reductions in the total corona current of around 29% and 42%, for positive and negative polarity, respectively. The corresponding reduction of ground-level ion currents and ion coupling with parallel conductors is expected to be of the same order of magnitude.