4.6 Article

Mitigation of Geomagnetically Induced Currents by Neutral Switching

期刊

IEEE TRANSACTIONS ON POWER DELIVERY
卷 30, 期 4, 页码 1999-2006

出版社

IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC
DOI: 10.1109/TPWRD.2015.2434411

关键词

Geomagnetic disturbance (GMD); geomagnetically induced current (GIC); geomagnetism; half-cycle saturation

向作者/读者索取更多资源

This paper presents a novel mitigation technique to reduce the effects of geomagnetically induced currents (GICs) on high-voltage power systems. The method consists of connecting switching devices at the neutral grounding connection point of transformer banks. Only one transformer bank needs to be grounded through a switch to reduce GIC in a two-terminal system. For multiterminal systems, n - 1 switches are necessary and the operation is independent from each other. The switching frequency and the duty cycle are selected from a tradeoff between the effectiveness of the method and the detection of fault currents. Transient simulations on a two-bus 230/500 kV system show that the proposed switching at the neutral successfully mitigates the GIC. This proposed technique opens the door to a new family of GIC mitigation methods.