4.4 Article Proceedings Paper

Comparison between measured and computed magnetic flux density distribution of simulated transformer core joints assembled from grain-oriented and non-oriented electrical steel

期刊

AIP ADVANCES
卷 8, 期 4, 页码 -

出版社

AMER INST PHYSICS
DOI: 10.1063/1.4994133

关键词

-

资金

  1. Baoshan Iron Steel Co. Ltd. [506076]
  2. National Major Research and Development Program of China [2016YFB 0300300]

向作者/读者索取更多资源

The flux distribution in an overlapped linear joint constructed in the central region of an Epstein Square was studied experimentally and results compared with those obtained using a computational magnetic field solver. High permeability grain-oriented (GO) and low permeability non-oriented (NO) electrical steels were compared at a nominal core flux density of 1.60 T at 50 Hz. It was found that the experimental results only agreed well at flux densities at which the reluctance of different paths of the flux are similar. Also it was revealed that the flux becomes more uniform when the working point of the electrical steel is close to the knee point of the B-H curve of the steel. (c) 2017 Author(s).