期刊
ENERGY ECONOMICS
卷 39, 期 -, 页码 128-134出版社
ELSEVIER SCIENCE BV
DOI: 10.1016/j.eneco.2013.04.011
关键词
Behavioral economics; Energy efficiency; Field experiments
类别
We describe a randomized controlled experiment in which the default settings on office thermostats in an OECD office building were manipulated during the winter heating season, and employees' chosen thermostat setting observed over a 6-week period. Using difference-in-differences, panel, and censored regression models (to control for maximum allowable thermostat settings), we find that a 1 degrees C decrease in the default caused a reduction in the chosen setting by 0.38 degrees C, on average. Sixty-five percent of this effect could be attributed to office occupant behavior (p-value = 0.044). The difference-in-differences models show that small decreases in the default (1 degrees) led to a greater reduction in chosen settings than large decreases (2 degrees). We also find that office occupants who were more apt to adjust their thermostats prior to the intervention were less susceptible to the default. We conclude that this kind of intervention can increase building-level energy efficiency, and discuss potential explanations and broader policy implications of our findings. (c) 2013 Elsevier B.V. All rights reserved.
作者
我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。
推荐