期刊
FRONTIERS OF ARCHITECTURAL RESEARCH
卷 2, 期 4, 页码 468-475出版社
ELSEVIER SCIENCE BV
DOI: 10.1016/j.foar.2013.09.003
关键词
Hospital operating room; Air conditioning; Computational fluid dynamics
类别
The goal of the air distribution inside a hospital operating room (OR) is to protect the patient and staff from cross-infection while maintaining occupant comfort and not affecting the facilitation of surgical tasks. In ORs, HEPA-filtered air and vertical (downward) laminar airflow are often used to achieve a unidirectional flow of fresh air from ceiling, washing over the patient and flowing out of exhaust vents on the side walls, near the floor. However, previous research has shown that this method does not necessarily achieve the desired unidirectional flow pattern or adequately achieve optimal air asepsis. The results from this study show that maximizing the area of the laminar flow diffusers remedies this issue and provides very low contamination levels. The use of air curtains as specified by manufacturers of commercial products may not provide satisfactory results, with noticeable contamination levels at the wound site. (C) 2013. Higher Education Press Limited Company. Production and hosting by Elsevier B.V.
作者
我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。
推荐