4.7 Article

Novel air-cooled condenser with V-frame cells and induced axial flow fans

期刊

出版社

PERGAMON-ELSEVIER SCIENCE LTD
DOI: 10.1016/j.ijheatmasstransfer.2017.09.139

关键词

Air-cooled condenser; Condenser cell; Induced axial flow fan; Flow and heat transfer; Turbine back pressure

资金

  1. National Natural Science Foundation of China [51476055]
  2. National Basic Research Program of China [2015CB251503]

向作者/读者索取更多资源

The thermo-flow performances of air-cooled condensers (ACCs) are basically deteriorated under wind conditions, so it is of great concerns to propose the measures against the adverse wind effects on aircooled condensers. In this work, a novel reconstruction of ACCs combined the V-frame condenser cells with the induced axial flow fans, and a modified layout of the novel ACCs for a specific wind direction are proposed based on the direct dry cooling system in a 2 x 600 MW power plant. The CFD approach with a validation is applied to the performance investigation of the novel ACCs. The variable fields, mass flow rate, inlet air temperature and turbine back pressure for both the conventional and novel layouts of ACCs under different wind conditions are obtained and compared. The results show that the mass flow rates of the novel ACCs increase conspicuously compared with the conventional ACCs both in the absence and presence of winds. The flow distortions through the induced axial flow fans are greatly restrained and the inlet air temperature of the novel ACCs decreases, which lead to the improved thermo-flow performances of ACCs and reduced turbine back pressure of power generating unit. (C) 2017 Elsevier Ltd. All rights reserved.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据