期刊
IEEE TRANSACTIONS ON POWER SYSTEMS
卷 33, 期 6, 页码 6476-6486出版社
IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC
DOI: 10.1109/TPWRS.2018.2854650
关键词
Power system transient stability; numerical integration; nonlinear dynamical systems
Once the critical clearing time of a fault leading to transient instability has been computed, it is desirable to quantify its dependence on system parameters. We derive, for a general power system model a new and exact formula for the first-order sensitivity of the critical clearing time with respect to any system parameter. The formula is evaluated by integrating variational equations forward in time along the base case fault-on trajectory and integrating adjoint variational equations backward in time along the postfault trajectory. The computation avoids recomputing the critical clearing time for each parameter change and gives insight into how parameters influence power system transient stability. The computation of the sensitivity of the critical clearing time with respect to load impedances and generator inertias is illustrated on a 39-bus system.
作者
我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。
推荐