期刊
IEEE TRANSACTIONS ON POWER DELIVERY
卷 33, 期 3, 页码 1492-1494出版社
IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC
DOI: 10.1109/TPWRD.2016.2580099
关键词
Live detection; partial discharge (PD); differential pulse method; oil-immersed inverted current transformer (OIICT)
资金
- China EPRI [GY71-14-004]
- China Postdoctoral Science Foundation [2015M572561]
This paper proposes the primary differential pulse method (PDPM) for the live partial-discharge (PD) detection of oil-immersed inverted current transformers. The PDPM is based on the differential current measurements that are taken at the high-voltage side of the current transformer under test. The proposed technique overcomes the problem of an internally grounded test tap and identifies the internal PD based on the polarities of current pulses. The PDPMdetection system is composed of current sensors, a data-acquisition module, a fiber-optics-based data-transmission module, and an operation mechanism with an insulating rod. The testing results prove that the designed system is effective for the live PD detection and can also effectively differentiate between PD and outside interference for oil-immersed inverted current transformers.
作者
我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。
推荐