4.6 Article

Fault Analysis of Inverter-Interfaced Distributed Generators With Different Control Schemes

期刊

IEEE TRANSACTIONS ON POWER DELIVERY
卷 33, 期 3, 页码 1223-1235

出版社

IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC
DOI: 10.1109/TPWRD.2017.2717388

关键词

Inverter-interfaced distributed generators (IIDGs); microgrid; fault current; limiter

资金

  1. National Natural Science Foundation of China [51622702]
  2. Higher National Excellent Doctoral Dissertation of Special Funds [201441]

向作者/读者索取更多资源

Diversification of control schemes adopted by inverter-interfaced distributed generators (IIDGs) leads to difficulties in fault current estimation in a microgrid, which might make preexisting protection systems invalid and threaten the safety of power electronic devices. It is therefore important to study fault characteristics of IIDGs. This paper investigates characteristics of fault current of IIDGs caused by both symmetrical and asymmetrical faults. Two kinds of widely used control modes, current control (constant current control and PQ control) and voltage control (V/F control and droop control), are under investigation to provide an intuitive comparison on fault current. In particular, a novel algorithm is proposed to calculate fault current of droop-controlled IIDGs. It is found that different limiters have great impacts on fault response of IIDGs and detailed research works are carried out to identify the effects in this paper. Simulation results based on PSCAD/EMTDC and calculation results based on MATLAB/Simulink verify the correctness of the proposed fault models.