Current transformer failure caused by electric field associated to circuit breaker and pollution in 500 kV substations

期刊

ENGINEERING FAILURE ANALYSIS
卷 92, 期 -, 页码 163-181

出版社

PERGAMON-ELSEVIER SCIENCE LTD
DOI: 10.1016/j.engfailanal.2018.05.017

关键词

Current transformer; Electric field; Creepage distance; Substations

资金

  1. Recognition of the company Red de Energia del Peru
  2. ENEL GREEN POWER
  3. Pontificia Universidad Catolica del Peru (PUCP), Doctoral Engineering Program
  4. FreePort-McMoRan Inc.

向作者/读者索取更多资源

In the last years, the power demand of Peril keeps rising and the power system expands the scale extraordinary, in order to transport more energy, the overhead lines and substations in 500 kV has been built, especially in the last decade. Currently, the international standards for the minimum safety distances in electrical substations have been designed considering the insulation co-ordination, however if some designer considers the equipment installed in the same phase, there are just a recommendation in some papers, without considers the effect of electric and magnetic field and contamination between assets. This research has analyzed a failure mode caused by electric field in 500 kV substations, the problem was focus on current transformers. Three current transformers have failed, exploiting near the circuit breakers in the same phase, the analysis and the root cause of this fault has been developed in a special condition, the coast of Peru, and the novel contribution is a recommendation for the physical layout in substations, insulation coordination and standards of electric field for the design of substations for 500kV.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据