期刊
APPLIED THERMAL ENGINEERING
卷 128, 期 -, 页码 1476-1487出版社
PERGAMON-ELSEVIER SCIENCE LTD
DOI: 10.1016/j.applthermaleng.2017.09.105
关键词
Solid desiccant; Maisotsenko cycle; Cross-flow HMX; Evaporative cooling
资金
- Energy Engineering Department of the University of Engineering and Technology Pakistan
This paper presents the performance investigation of a solid desiccant dehumidifier integrated with Maisotsenko cycle (M-Cycle) based cross flow heat and mass exchanger (MC-DAC). The experimental test rig consisting of a silica gel based desiccant wheel and a heat recovery wheel is coupled with M-Cycle indirect evaporative cooler. The effect of wide range of inlet air parameters such as ambient temperature, humidity ratio, and regeneration temperature on the performance of integrated system was analyzed and compared with the conventional desiccant air conditioning (DAC) system. Set of experiments were carried out for both systems at constant process as well as return air mass flow rates under different operating conditions. MC-DAC system was observed to be around 60-65% more efficient than the other system in terms of COPth providing same supply air conditions at low regeneration temperatures. (C) 2017 Elsevier Ltd. All rights reserved.
作者
我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。
推荐