4.7 Article

A quantitative approach identifies the critical flow characteristics in a natural draft dry cooling tower

期刊

APPLIED THERMAL ENGINEERING
卷 131, 期 -, 页码 522-530

出版社

PERGAMON-ELSEVIER SCIENCE LTD
DOI: 10.1016/j.applthermaleng.2017.12.038

关键词

NDDCT; Hot state experiment; Crosswind; FLF; Quantitative description; Flow separation

资金

  1. National Natural Science Foundation of China [L1522032]
  2. Chinese Engineering Academy [2015-ZCQ-06]
  3. State Key Lab of Power Systems [SKLD13KZ05]

向作者/读者索取更多资源

The natural draft dry cooling tower (NDDCT) is a critical facility for an indirect dry cooling power plant in arid area for its merit of excellent water-saving. While crosswind degrades the performance of a NDDCT by changing the flow field inside and outside. In order to quantitatively study the influence of different flow characteristics on the performance of a NDDCT, hence to grasp the affecting mechanism of crosswind, a half-cylindrical computational fluid dynamics (CFD) model of a Heller type 660 MW NDDCT is developed and validated by a hot state modelling test rig. A flow loss factor (FLF) is derived and verified to linearly describe the effect of local flow field changing on the overall performance of a NDDCT. Based on the conjoint studies of the local FLF variation trends and the changing processes of correspondent flow characteristics in each specific flow segments, the critical factors influencing the performance of a NDDCT are identified under different crosswind conditions. (C) 2017 Elsevier Ltd. All rights reserved.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据