A Current Limiting Strategy to Improve Fault Ride-Through of Inverter Interfaced Autonomous Microgrids

期刊

IEEE TRANSACTIONS ON SMART GRID
卷 8, 期 5, 页码 2138-2148

出版社

IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC
DOI: 10.1109/TSG.2016.2517201

关键词

Current control; fault current limiters; fault ride-through (FRT); reference frame; transient response; voltage limit; voltage-sourced inverter (VSI)

向作者/读者索取更多资源

With high penetration of distributed energy resources, fault management strategy is of great importance for the distribution network operation. The objective of this paper is to propose a current and voltage limiting strategy to enhance fault ride-through (FRT) capability of inverter-based islanded microgrids (MGs) in which the effects of inverter control system and inverter topology (four/three-wire) are considered. A three-phase voltage-sourced inverter with multi-loop control system implemented in synchronous, stationary, and natural reference frames is employed in this paper for both four-and three-wire configurations. The proposed strategy provides high voltage and current quality during overcurrent conditions, which is necessary for sensitive loads. Several time-domain simulation studies are conducted to investigate the FRT capability of the proposed strategy against both asymmetrical and symmetrical faults. Moreover, the proposed method is tested on the CIGRE benchmark MG to demonstrate the effectiveness of the proposed limiting strategy.