3.8 Proceedings Paper

Performance of R407C as an Alternate to R22: A Review

出版社

ELSEVIER SCIENCE BV
DOI: 10.1016/j.egypro.2017.03.032

关键词

R22 Phaseout; Ozone deletion potential; Global warming potential; R407C

向作者/读者索取更多资源

The outcome of R407C as a drop in replacement of R22 has been reviewed in this paper. As per Montreal Protocol, R22 is going to be phase out due to its unfavourable impacts related to environment e.g. ozone depletion potential (ODP) and global warming potential (GWP). R407C has zero ODP and considerably GWP as compared to R22. The releasing of refrigerants in the surroundings becomes the cause of issues pertinent in environment. A detailed review about the experimental studies associated with the performance of R407C is provided. The aim is to put together all the diversified information about the R407C in a single paper. It is found after the careful observation that R22 performs somewhat better than R407C in many aspects i.e. COP, Cooling Capacity, Energy Consumption, and Exergetic Analysis but retrofitting point of view, it is best suitable refrigerant and R410A is suitable for new design. (C) 2017 The Authors. Published by Elsevier Ltd.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

3.8
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据