4.7 Article

Theoretical prediction of acid dew point and safe operating temperature of heat exchangers for coal-fired power plants

期刊

APPLIED THERMAL ENGINEERING
卷 123, 期 -, 页码 782-790

出版社

PERGAMON-ELSEVIER SCIENCE LTD
DOI: 10.1016/j.applthermaleng.2017.05.051

关键词

Iterative calculation model; Acid dew point; Safe operating temperature; Low temperature corrosion

向作者/读者索取更多资源

Research on acid dew point and condensation process of flue gas is necessary for making full use of waste heat in coal-fired boilers and reducing low temperature corrosion of heat exchangers. The iterative calculation of acid condensation is studied with consideration of both the gas-liquid equilibrium effect and multi-component diffusion effect. Furthermore, based on the thermodynamic data of water vapor and sulfuric acid vapor, the iterative calculation model of the acid dew point is proposed. The iteration result shows great consistency with the experimental data, and with the maximum and minimum deviation being around 2.68 degrees C and 2.07 degrees C, respectively. The single-factor and orthogonal calculations are analyzed to obtain the effects of temperature, acid vapor content and water vapor content on the acid condensation. In addition, the safe operating temperature of heat exchanger is suggested based on the analysis of corrosion mechanism and acid condensation calculation results. The lowest temperature of heat exchanger is recommended above 80 degrees C in the practical application of waste heat utilization in coal-fired boilers. (C) 2017 Published by Elsevier Ltd.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据