Model predictive control of radiant slab systems with evaporative cooling sources

期刊

ENERGY AND BUILDINGS
卷 87, 期 -, 页码 199-210

出版社

ELSEVIER SCIENCE SA
DOI: 10.1016/j.enbuild.2014.11.037

关键词

Radiant slab systems; Evaporative cooling; Model predictive control; Energy and comfort performance; Calibrated simulation

资金

  1. California Energy Commission (CEC) Public Interest Energy Research (PIER) Buildings Program [CEC 500-08-004]
  2. Center for the Built Environment, University of California, Berkeley

向作者/读者索取更多资源

Buildings that use radiant slab systems with evaporative cooling sources have shown to be energy efficient. However, control of the systems is challenging because of the slow response of the slab and the limited capacity of cooling sources. The objectives of this paper are to: (1) create a simplified dynamic model of radiant slab system for implementation in real-time model predictive controller (MPC); and (2) test the MPC energy and thermal comfort performance in a case study building. A calibrated EnergyPlus model of the building was developed as the testbed. The MPC is compared with the existing rule-based control method for a cooling season in a dry and hot climate. The results indicated that the MPC controller was able to maintain zone operative temperatures at EN 15251 Category II level more than 95% of the occupied hours for all zones, while with the rule-based method, only the core zone were maintained at this thermal comfort level. Compared to the rule-based method, MPC reduced the cooling tower energy consumption by 55% and pumping power consumption by 25%. (C) 2014 Elsevier B.V. All rights reserved.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据