4.7 Article

Variable evaporating temperature control strategy for VRV system under part load conditions in cooling mode

期刊

ENERGY AND BUILDINGS
卷 91, 期 -, 页码 180-186

出版社

ELSEVIER SCIENCE SA
DOI: 10.1016/j.enbuild.2015.01.039

关键词

VRV; Variable evaporating temperature; Part load condition; Control strategy

资金

  1. company of Daikin China

向作者/读者索取更多资源

Control strategy is key technology for efficient and reliable operation of air conditioning system. Although VRV research is booming in recent years, the general control strategy of VRV system is still to regulate refrigerant flow rate while keeping evaporating temperature or discharge pressure constant during cooling or heating process. In this paper, a novel control strategy with variable evaporating temperature is explored under part load conditions. Based on running point determined by original control strategy, the new strategy further reduces running frequency under the same part load conditions. Correspondingly, energy consumption reduces and evaporating temperature rises. Theoretical analysis proves its feasibility of energy saving. Further experimental results show that the novel control strategy would help to improve VRV system energy efficiency and reduce cooling energy consumption especially for part load conditions lower than 50%. (C) 2015 Elsevier B.V. All rights reserved.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据