Assessing flammable storage cabinets as sources of VOC exposure in laboratories using real-time direct reading wireless detectors

期刊

JOURNAL OF CHEMICAL HEALTH & SAFETY
卷 25, 期 5, 页码 2-9

出版社

ELSEVIER SCIENCE INC
DOI: 10.1016/j.jchas.2018.01.001

关键词

-

资金

  1. National Science Foundation [CHE-1566438]
  2. CDC Center for Control Disease and Prevention through LASSI fund

向作者/读者索取更多资源

Herein we present the results of measurements using wireless direct-reading photoionization detector-based gas sensors to quantify concentrations of vapors of volatile organic compounds (VOCs) in and around flammable storage cabinets containing common organic solvents, including acetone, dichloromethane, trichloroethylene, and benzene. Such cabinets are commonly employed in laboratories to contain flammable liquids. A sensor array was deployed in a series of flammable storage cabinets in working laboratories. Measurements in cabinets containing bottles of typical solvents demonstrate that vapor concentrations gradually increase upon closing the cabinet door. The results suggest that these storage units can be a source of vapors of VOCs in laboratories and the unnecessary exposure of laboratory workers to chemical vapors. Ventilation of cabinets tended to lower maximum concentrations of VOCs. However, the efficacy of this engineering control was found to depend on the quality of the cabinet door seal, as well as having debris-free flame arrestors. Opening cabinet doors resulted in release of vapors to the laboratory atmosphere, which represents an unnecessary exposure risk for workers. A countermeasure aimed at improving the seal of previously opened solvent bottles reduced measured concentrations of VOCs in cabinets below the detector's limit of detection.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

3.8
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据