16TH INTERNATIONAL SYMPOSIUM ON DISTRICT HEATING AND COOLING, DHC2018
卷 149, 期 -, 页码 197-205出版社
ELSEVIER SCIENCE BV
DOI: 10.1016/j.egypro.2018.08.184
关键词
Heat Booster Station; Ultra Low Temperature District Heating; Load Shift; Heat Pump; 4th Generation District Heating
资金
- Danish EUDP
Ultra-low temperature district heating (ULTDH) substations may be an important enabler for integrating higher shares of renewables and waste heat in the district heating (DH) network. In the paper, we describe a concept and first experimental results for producing domestic hot water (DHW) at DH supply temperatures of 45 degrees C. The substation utilises a heat pump for boosting the DH temperature up to approximately 60 degrees C to an accumulation tank, after which the DHW can be produced on demand for temperatures up to 55 degrees C. Additionally, the system included a separate heat pump to supply the DHW circulation heat demand The DH accumulator tank provides load shift opportunities, which is important going towards the integrated, flexible and renewable based future energy system. The two heat pumps operate with a COP of approximately 5, which results in representative share of approximately 11-13 % electricity to supply the DHW including circulation. (C) 2018 The Authors. Published by Elsevier Ltd.
作者
我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。
推荐
暂无数据