期刊
JOURNAL OF BUILDING ENGINEERING
卷 22, 期 -, 页码 372-382出版社
ELSEVIER
DOI: 10.1016/j.jobe.2019.01.004
关键词
Chilled ceiling; Cooling ceiling; PCM; Phase change material; TRNSYS; Type 399; Type 56
资金
- Federal Ministry for Economic Affairs and Energy, Germany [03ET1245A]
The evaluation and optimization of innovative building systems with simulation programs requires validated models. This paper describes a new room model for an innovative chilled ceiling with PCM (phase change materials) for the simulation program TRNSYS. The room model was validated using laboratory measurements and monitoring data of a real scale building. The chilled PCM ceiling model uses the TRNSYS type 399, which originally was made for simulating massive thermo-active building elements with PCM. This article shows, that type 399 also can be used for the chilled PCM ceiling, if certain constraints in the model geometry are taken into account. The validated model shows a good agreement with the real scale building data. A root mean square error (RMSE) for the deviation of simulated and measured temperatures of +/- 0.3 degrees C and +/- 0.6 degrees C could be achieved for the operative and PCM temperature, respectively. The simulated cooling power of the PCM ceiling showed a higher deviation, the RMSE was +/- 0.19 kW. In a next step, the validated room model will be used to optimize the control of the chilled PCM ceiling system in a real scale building.
作者
我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。
推荐
暂无数据