4.7 Article

Numerical study of thermal management of data centre using porous medium approach

期刊

JOURNAL OF BUILDING ENGINEERING
卷 22, 期 -, 页码 200-215

出版社

ELSEVIER SCIENCE BV
DOI: 10.1016/j.jobe.2018.12.012

关键词

Data centre; Porous medium; Thermal management; Recirculation; Cold air bypass; Heat generation

向作者/读者索取更多资源

In this paper, the numerical study of thermal performance of a data centre using porous medium approach to model a rack server considering the cooling fans mounted on the rear side of the servers as momentum source terms is presented. Fluid flow and heat transfer in the data centre room are predicted and evaluated to understand the effects of hot-air recirculation and cold air bypass on the temperature distribution using thermal performance parameters, such as supply/return heat index (SHI/RHI), return temperature index (RTI) and rack cooling index (RCI). The results reveal that the outlet vent placed at the bottom of the wall facing the hot aisle is the best configuration to reduce the maximum temperature observed inside the racks. The homogeneous volumetric heat generation insignificantly affects the values of SHI/RHI and RTI, when the porosities of the racks are same. It is found that a certain arrangement of racks with variable porosity results in better cooling effects.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据