The capacity of distributed generators (DGs) connected to a grid by inverters is growing. The inverters are generally controlled by a phase locked loop (PLL) in order to achieve synchronization with the power system frequency. They cannot have synchronous power. Power systems become unstable if the capacity of the inverter-type DGs is increased. The concept of controlling inverters to behave like a synchronous generator is studied in this paper. The result is referred to as a virtual synchronous generator (VSG). The VSG has synchronous power. Power systems become stable as a result of using the VSG. The VSG is useful in the parallel operation of DGs. The VSG can synchronize with other VSGs, synchronous generators, or the grid. In this paper, a method for the synchronous operation of a VSG is studied, and experimental results on a VSG running in parallel with a synchronous generator and other VSGs are presented.