Effect of parameters on moisture removal capacity in the desiccant cooling systems

期刊

出版社

ELSEVIER
DOI: 10.1016/j.csite.2018.11.015

关键词

Moisture; Desiccant; Cooling system; Silica gel; Molecular sieve; Indoor humidity

向作者/读者索取更多资源

A mathematical model was developed to investigate the effect of crucial operating parameters, such as process inlet humidity ratio, inlet volume flow rate, R/P ratio (reactivation/process air flow), regenerative temperature and rotational speed on the performance of desiccant wheels in hot and humid climates, using wound silica gel and molecular sieve desiccants. The desiccant wheels were designed to operate in two modes, specifically, with 90 degrees for reactivation and 270 degrees for process (1:3 split) as well as with 180 degrees for reactivation and 180 degrees for process (1:1 split). The main results enabled to make the following observations: (i) higher regeneration air temperature leads to an improvement of dehumidification and reduction of the thermal coefficient of performance COPth, (ii) an increase in the process inlet volume flow rate causes a reduction in the process removed moisture; (iii) the greater R/P ratio is required to remove more moisture, while a lower R/P ratio implies the lower power consumption for regeneration; (iv) silica gel desiccant is preferred when greater moisture removal is required at high inlet relative humidity, while molecular sieve desiccant is preferred when low dew point is required at low inlet relative humidity.