4.5 Article

Stability and Dynamic Analyses of Transmission Tower-Line Systems Subjected to Conductor Breaking

出版社

WORLD SCIENTIFIC PUBL CO PTE LTD
DOI: 10.1142/S0219455417710134

关键词

Transmission tower-line system; conductor breaking; stability analysis; dynamic impact; collapse simulation

资金

  1. National Natural Science Foundation of China [51421064]

向作者/读者索取更多资源

Ice loads exerted on the transmission line can increase the probability of conductor breaking, which will lead to the stability failure of transmission towers. In this paper, a transmission tower-line system is established for two towers and three span lines. Then the nonlinear static stability analysis and nonlinear dynamic stability analysis induced by the conductor breaking are carried out to obtain the load versus displacement curves, while studying the failure modes of the transmission tower-line system. Moreover, the ice load and initial eccentricity are considered in the numerical simulation. In addition, a parametric analysis is performed to investigate the influence of span, insulator length and initial tension force on the stability failure of the system. The results show that the dynamic instability will occur earlier than the static instability due to the dynamic impact effect and conductor breaking with ice loads can lead to the progressive collapse of the transmission tower-line system. Finally, the span length has the greatest effect on the response of transmission tower caused by conductor breaking.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.5
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据