4.5 Article

Performance analysis of vapor compression refrigeration system using an adaptive neuro-fuzzy inference system

出版社

ELSEVIER SCI LTD
DOI: 10.1016/j.ijrefrig.2017.06.019

关键词

ANFIS; R134a/LPG; Vapor compression refrigeration; system; COP

资金

  1. IKGPTU Kapurthala
  2. BCET Gurdaspur

向作者/读者索取更多资源

In this work, an experimental investigation is carried out with R134a and LPG refrigerant mixture (composed of R134a and LPG in the ratio of 28: 72 by weight) as an alternative to R134a in a vapor compression refrigeration system. Performance tests were performed with different evaporator temperatures under controlled ambient conditions. The results showed that the R134a/LPG mixture has a higher coefficient of performance (COP) than R134a by about 15.28% in the studied range. The applicability of adaptive neuro-fuzzy inference system (ANFIS) to predict the COP of R134a/LPG system was also investigated. An ANFIS model for the system was developed. The comparison of statistical analysis of mathematical and ANFIS model predictions respectively in terms of the absolute fraction of variance (0.982 and 0.994), the root mean square error (0.0056 and 0.0050) and the mean absolute percentage error (0.286% and 0.217%) showed that ANFIS model gave the better statistical prediction efficiency. (C) 2017 Elsevier Ltd and IIR. All rights reserved.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.5
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据