Adaptive Autoreclosing Scheme for Line-to-Line Nongrounded Faults on Double-Circuit Transmission Lines Based on Phase-to-Phase Reactive Power

期刊

IEEE ACCESS
卷 8, 期 -, 页码 144092-144104

出版社

IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC
DOI: 10.1109/ACCESS.2020.3014179

关键词

Circuit faults; Power transmission lines; Discrete cosine transforms; Oscillators; Reactive power; Adaptive algorithm; current-voltage characteristics; fault detection; grounding; power system protection; power system reliability; reactive power; transmission lines

资金

  1. National Natural Science Foundation of China [51877185]
  2. Scientific Research Project of Shihezi University [ZZZC201736B]

向作者/读者索取更多资源

Double-circuit transmission lines play a very important role in electric power transmission. When a line-to-line nongrounded fault occurs on double-circuit transmission lines, for traditional tripping and reclosing methods, tripping of all six phases may cause power system instability, and fixed time autoreclosing may reclose the double-circuit transmission lines to a nonextinguished fault. In this paper, a novel tripping strategy is proposed; when a line-to-line nongrounded fault occurs, some part of the electric power can be transmitted after tripping, and many kinds of nongrounded faults can be equivalent to a single-phase to ground fault. Furthermore, reactive power characteristics are adopted to determine the fault extinction. Finally, an adaptive autoreclosing scheme for line-to-line nongrounded faults on double-circuit transmission lines based on phase-to-phase reactive power is proposed. The accuracy and feasibility of the propose method are verified by relevant simulation experiments, and multiple operation conditions are considered.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.6
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据