Fast-Frequency Response Provided by DFIG-Wind Turbines and its Impact on the Grid

期刊

IEEE TRANSACTIONS ON POWER SYSTEMS
卷 32, 期 5, 页码 4002-4011

出版社

IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC
DOI: 10.1109/TPWRS.2016.2636374

关键词

Ancillary services; doubly-fed induction generator; fast-frequency response; primary frequency control; wind power integration

资金

  1. SENESCYT, Government of the Republic of Ecuador [2015-AR6C5141]

向作者/读者索取更多资源

This paper presents a methodology for the analysis of frequency dynamics in large-scale power systems with high level of wind energy penetration by means of a simplified model for DFIG-based wind turbines. In addition, a virtual inertia controller version of the optimized power point tracking (OPPT) method is implemented for this kind of wind turbines, where the maximum power point tracking curve is shifted to drive variations in the active power injection as a function of both the grid frequency deviation and its time derivative. The proposed methodology integrates the model in a primary frequency control scheme to analyze the interaction with the rest of the plants in the power system. It is also proven that, under real wind conditions, the proposed version of the OPPT method allows us to smooth the wind power injected into the grid, thereby reducing frequency fluctuations.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据